Monday, February 22, 2016


New Video Release - From the Desk of Codes and Standards (Tray Cable 101)

Join Encore Wire's Manager of Codes and Standards as he explains the construction and uses of Type TC Cable and answered a few questions on it's use. Join Paul as he gives you a better understanding of Type TC (Tray Cable) from a manufacturers perspective.


New Video Release - From the Desk of Codes and Standards (Type MC-LED)

Join Encore Wire's Manager of Codes and Standards as he explains the construction and uses of Type MC-LED and answered a few questions on it's use. This episode explains the misconception about the use of Type MC-LED in environmental air spaces (plenum) and for uses other than just for lighting systems.





Wired for Healthcare...

Just What the Doctor Ordered.

McKinney, TX., January 1, 2016 – Encore Wire introduced to their manufacturer representatives their newest addition in the existing Type MC-LED (Type PCS) product line, MC-LED HealthcareTM, the next generation of Encore’s hybrid power and control/signal conductor cable system. MC-LED Healthcare incorporates Encore’s advanced SmartGroundTM technology, which provides the required redundant grounding path demanded by Section 517.13(a) of the National Electrical Code® for use in patient care areas of hospitals, nursing homes, dental offices, outpatient and other types of healthcare facilities.

"As emerging energy saving technology rapidly expands in the 21st century, so should the cabling technology that powers the world's energy conservation. Encore Wire’s Type MC-LED Healthcare cable was specifically designed to adapt and overcome existing cable limitations with proven innovative solutions.”- Paul Abernathy, Encore Wire Codes & Standards Manager.

MC-LED Healthcare is ideal for use in 0-10V dimming control and energy management systems in health care facilities where energy management is critical to effective and sustainable operations. Encore’s specialized redundant grounding system features a bare aluminum bonding/grounding conductor installed in intimate contact with all convolutions within the armored cable system, which ensures a more effective and reliable grounding system in health care environments where grounding and bonding redundancy is critical to environmental safety. MC-LED Healthcare is available with 12 AWG or 10 AWG CU Type THHN/THWN-2 power conductors, along with an individually twisted and jacketed pair of 16 AWG CU Type TFN or equivalent conductors.

For more information about Encore Wire's MC-LED Healthcare, please contact Kyle Carter at 972.562.9473 ext. 277 or visit encorewire.com. For our Codes & Standards video, go to youtube.com.

About Encore Wire
Encore Wire Corporation is a leading manufacturer of a broad range of electrical building wire for interior wiring in commercial and industrial buildings, homes, apartments, and manufactured housing. The Company is focused on maintaining a high level of customer service with low-cost production and the addition of new products that complement its current product line. To learn more about Encore Wire, its products and culture, visit encorewire.com, YouTube, and Facebook.



Encore Wire Corporation
1329 Millwood Road
McKinney, TX 75069
972.562.9473
www.encorewire.com

Media Contact:
Karolina Zuraw
Marketing Manager
karolina.zuraw@encorewire.com
972.562.9473 Ext. 210

Monday, July 14, 2014

Encore's Codes and Standards Manager Appointed



McKinney, TX -

Encore Wire Corporation's codes and standards manager Paul W. Abernathy was selected on July 14, 2014 as a Subject Matter Expert [SME] to assist in developing and maintaining the State of Texas Electrical Exams. Paul will also serve as a core member of the Texas Electrical Development Exam Committee.

Mr. Abernathy also serves on the North Texas Electrical Advisory Committee on behalf of Encore Wire Corporation and the Citizens of Northern Texas.

Wednesday, July 2, 2014

Can NM-B Cable be installed in a Wet or Damp Location?


On occasion we receive a specific question about installing Nonmetallic-Sheathed Cable [NM-B] in wet and damp locations. Here at Encore Wire we figured it was time to explain the use of NM-B in these locations.

The first place to start is by understanding what a Dry, Damp, and Wet location actually is. The National Electrical Code®[NEC®] addresses each of these items in Article 100.

Location, Dry. A location not normally subject to dampness or wetness. A location classified as dry may be temporarily subject to dampness or wetness, as in the case of a building under construction.

Location, Damp. Locations protected from weather and not subject to saturation with water or other liquids but subject to moderate degrees of moisture.

Location, Wet. Installations underground or in concrete slabs or masonry in direct contact with the earth; in locations subject to saturation with water or other liquids, such as vehicle washing areas; and in unprotected locations exposed to weather.

Once you have established the location where the NM-B Cable is going to be located, you then have to examine it even closer. Many people believe that NM-B Cable installed in liquidtight flexible nonmetallic conduit [LFNC] outside abovegrade is acceptable simply because it is installed in liquidtight. However, that would be incorrect based on Section 300.9 of the NEC which states "Raceways in Wet Locations Abovegrade. Where raceways are installed in wet locations abovegrade, the interior of these raceways shall be considered to be a wet location. " and lets never forget that Section 300.5(B) says when installing underground "The interior of enclosures or raceways installed underground shall be considered to be a wet location."

NEC Section 334.10(A)(1) specifically permits NM Cable in both exposed and concealed work in normally dry locations it's actually Section 334.12(B)(4) that states NM Cable is not permitted in Wet or Damp location.

At the end of the day the AHJ will have to make the final call. However, with the guidance of Article 100, Section 300.9, and Article 334 we are confident the reader of this article will make the Right Call !


Understanding 310.15(B)(7) of the 2014 NEC®


With the recent publication of the 2014 National Electrical Code® [NEC®] many code savvy users are noticing some minor changes and a few seemingly complex code changes that took place during the recent code update process. One of those changes we will blog about today is the change to Section 310.15(B)(7). Code users who navigate to Section 310.15(B)(7) will notice right away that the familiar table we have all become accustom to is missing from the NEC.

As a result of extensive review by Code Making Panel #6; the familiar table was deleted and replaced with code language describing a calculation required by the code user. The efforts behind this change is to ensure that code users apply the correct corrections and adjustments factors to service and feeders that use 310.15(B)(7) and to simplify the intent of the code. Previous references to "main power feeder" have been removed.

Let's establish that 310.15(B)(7) only applies to 120/240 Volt, Single-Phase Dwelling Services and Feeders that are associated with one-family dwellings, and the individual dwelling units of two-family and multifamily dwelling units. This code allowance only applies to services and feeders rated 100 through 400 Amps that serve 100 % of the dwelling load.

First we have to understand which conductors this rule applies too, examine the code text below.

"the service conductors supplying the entire load associated with a one-family dwelling, or the service conductors supplying the entire load associated with an individual dwelling unit in a two-family or multifamily dwelling" and " the feeder conductors supplying the entire load associated with a one-family dwelling, or the feeder conductors supplying the entire load associated with an individual dwelling, unit in a two-family or multifamily dwelling" 

Once established that 310.15(B)(7) can apply; we bring in the calculation values to be considered. shall be permitted to have an ampacity not less than 83 percent of the service rating or feeder rating ; depending on which we are working with. Lets look at an example.

Example:
If a 175-ampere service rating is selected, a service conductor is then sized as follows:

175 amperes × 0.83 = 145.25 amperes per 310.15(B)(7).

If no other adjustments or corrections are required for the installation, then, in accordance with Table 310.15(B)(16), a 1/0 AWG Cu or a 3/0 AWG Al meets this rating at 75°C (167°F).

Lastly it is important to emphasize that any adjustments or corrections do have to be applied in determining the final ampacity value of a conductor, and you do have to use the standard ampacity table at 310.15(B)(16). The move from a table to a calculation ensures that the end user understands that other conditions may apply that can change a conductors ampacity versus simply pulling a figure from a table and assuming it is the final acceptable value.

If you have additional questions, need more clarification, or simply would like to suggest other topics to discuss please submit them to Codes and Standards.