Monday, July 14, 2014

Encore's Codes and Standards Manager Appointed



McKinney, TX -

Encore Wire Corporation's codes and standards manager Paul W. Abernathy was selected on July 14, 2014 as a Subject Matter Expert [SME] to assist in developing and maintaining the State of Texas Electrical Exams. Paul will also serve as a core member of the Texas Electrical Development Exam Committee.

Mr. Abernathy also serves on the North Texas Electrical Advisory Committee on behalf of Encore Wire Corporation and the Citizens of Northern Texas.

Wednesday, July 2, 2014

Can NM-B Cable be installed in a Wet or Damp Location?


On occasion we receive a specific question about installing Nonmetallic-Sheathed Cable [NM-B] in wet and damp locations. Here at Encore Wire we figured it was time to explain the use of NM-B in these locations.

The first place to start is by understanding what a Dry, Damp, and Wet location actually is. The National Electrical Code®[NEC®] addresses each of these items in Article 100.

Location, Dry. A location not normally subject to dampness or wetness. A location classified as dry may be temporarily subject to dampness or wetness, as in the case of a building under construction.

Location, Damp. Locations protected from weather and not subject to saturation with water or other liquids but subject to moderate degrees of moisture.

Location, Wet. Installations underground or in concrete slabs or masonry in direct contact with the earth; in locations subject to saturation with water or other liquids, such as vehicle washing areas; and in unprotected locations exposed to weather.

Once you have established the location where the NM-B Cable is going to be located, you then have to examine it even closer. Many people believe that NM-B Cable installed in liquidtight flexible nonmetallic conduit [LFNC] outside abovegrade is acceptable simply because it is installed in liquidtight. However, that would be incorrect based on Section 300.9 of the NEC which states "Raceways in Wet Locations Abovegrade. Where raceways are installed in wet locations abovegrade, the interior of these raceways shall be considered to be a wet location. " and lets never forget that Section 300.5(B) says when installing underground "The interior of enclosures or raceways installed underground shall be considered to be a wet location."

NEC Section 334.10(A)(1) specifically permits NM Cable in both exposed and concealed work in normally dry locations it's actually Section 334.12(B)(4) that states NM Cable is not permitted in Wet or Damp location.

At the end of the day the AHJ will have to make the final call. However, with the guidance of Article 100, Section 300.9, and Article 334 we are confident the reader of this article will make the Right Call !


Understanding 310.15(B)(7) of the 2014 NEC®


With the recent publication of the 2014 National Electrical Code® [NEC®] many code savvy users are noticing some minor changes and a few seemingly complex code changes that took place during the recent code update process. One of those changes we will blog about today is the change to Section 310.15(B)(7). Code users who navigate to Section 310.15(B)(7) will notice right away that the familiar table we have all become accustom to is missing from the NEC.

As a result of extensive review by Code Making Panel #6; the familiar table was deleted and replaced with code language describing a calculation required by the code user. The efforts behind this change is to ensure that code users apply the correct corrections and adjustments factors to service and feeders that use 310.15(B)(7) and to simplify the intent of the code. Previous references to "main power feeder" have been removed.

Let's establish that 310.15(B)(7) only applies to 120/240 Volt, Single-Phase Dwelling Services and Feeders that are associated with one-family dwellings, and the individual dwelling units of two-family and multifamily dwelling units. This code allowance only applies to services and feeders rated 100 through 400 Amps that serve 100 % of the dwelling load.

First we have to understand which conductors this rule applies too, examine the code text below.

"the service conductors supplying the entire load associated with a one-family dwelling, or the service conductors supplying the entire load associated with an individual dwelling unit in a two-family or multifamily dwelling" and " the feeder conductors supplying the entire load associated with a one-family dwelling, or the feeder conductors supplying the entire load associated with an individual dwelling, unit in a two-family or multifamily dwelling" 

Once established that 310.15(B)(7) can apply; we bring in the calculation values to be considered. shall be permitted to have an ampacity not less than 83 percent of the service rating or feeder rating ; depending on which we are working with. Lets look at an example.

Example:
If a 175-ampere service rating is selected, a service conductor is then sized as follows:

175 amperes × 0.83 = 145.25 amperes per 310.15(B)(7).

If no other adjustments or corrections are required for the installation, then, in accordance with Table 310.15(B)(16), a 1/0 AWG Cu or a 3/0 AWG Al meets this rating at 75°C (167°F).

Lastly it is important to emphasize that any adjustments or corrections do have to be applied in determining the final ampacity value of a conductor, and you do have to use the standard ampacity table at 310.15(B)(16). The move from a table to a calculation ensures that the end user understands that other conditions may apply that can change a conductors ampacity versus simply pulling a figure from a table and assuming it is the final acceptable value.

If you have additional questions, need more clarification, or simply would like to suggest other topics to discuss please submit them to Codes and Standards.

National Electrical Code and NEC are registered trademarks of the National Fire Protection Association [NFPA].

EC&M Product of the Year-

Encore wins 2014 EC&M Product of the Year in the Wire & Cable Equipment category for the Reel Payoff, the industry’s first self-spinning wooden reel.
Check out our video at http://www.encorewire.com/product-videos/

Encore Wire makes Forbes.com America’s 100 Most Trustworthy Companies for the second time

We did it again! Forbes.com  released its 2014 list of America’s 100 Most Trustworthy Companies and Encore Wire Corporation was selected from among thousands for its accounting transparency and strong stock performance. This is Encore’s second time to make the America’s 100 Most Trustworthy Companies list with a previous listing in 2012.

Encore Wire Corporation hires Codes and Standards Manager


McKinney, TX- Encore Wire Corporation is pleased to announce the hiring of Paul W. Abernathy as Encore Wire's New Manager of Codes and Standards.

Mr. Abernathy brings 28 years of experience as a licensed master electrician, certified electrical inspector, certified electrical plans examiner, technical code author/columnist, and electrical code technical expert to an already well established team of Codes and Standards professional here at Encore Wire.

Encore Wire Corporation strives for the highest level of quality and customer service. With the expansion of the Codes and Standards division; Encore Wire begins the quest to be your one-stop resource for all things National Electrical Code® and Product Standard related. Click Here to Contact "Codes and Standards" Today !